The influence of the elements of the mounting frame of a ventilated facade on building thermal losses

Abstract

The influence of the elements of the mounting frame of a ventilated facade on building thermal losses

Misirova A. M., Misirov M. H., Hasauov Ju. M.

Incoming article date: 03.05.2017

Obtained in the course of work the results show that the heat loss through fasteners ventilated facade is 40.5% of the total heat loss through the outer face of the facade. Using the data obtained for the evaluation of the heat losses of a 7 - storey residential building in the city of Nalchik, with a total area of external walling 2.470 sq. m. found that at a temperature difference of 39°C for 1 hour in the wall is the thermal energy in the amount of 57 kW«h, including 23.1 kW«h refer to the heat loss via the fastening elements of the facade panels, for 24 hours through heat-conducting inclusions is lost 554.4 kW«h For 7 months of the heating period with an average temperature of 28°C the heat loss will be 83745.7 kW«h Taking the cost of 1 kW«h of electricity 3.47 RUB and assess the rate of heat loss through the frame of a ventilated facade in cash for the entire heating period, will receive additional heat loss through the frame of a ventilated facade cost 290597 RUB.

Keywords: temperature field, heat-conducting inclusions, ventilated facade, heat, heat flux, fasteners