The study of room's air exchange scheme's influence on exhaust ventilation hood's effectiveness

Abstract

The study of room's air exchange scheme's influence on exhaust ventilation hood's effectiveness

Pukhkal V.A., Pankov V.B.

Incoming article date: 12.07.2020

The study is set to determine room's air exchange scheme's influence on exhaust ventilation appliances' effectiveness. Open-type exhausts (exhaust ventilation hoods) used in different industrial manufacturing processes are selected. In particular, a food processing working space with an adjacent meat heat-treating chamber, where ventilation hood is installed near an open doorway, is evaluated. Two options of supply air ducts' installation (air inflow in the center of a working space or, alternatively, side areas of it) are analysed. Geometrical models of heat-treating chamber, raw material loading room, ventilation hood placed over chamber's door, and supply air duct with air-distributing appliances are constructed. The article presents results of numerical simulation for the model of heat-treating chamber's exhaust ventilation system operation. It is established that, in case of a supply ducts' installation in a side areas of a room, an air exchange could be lowered by 28% under condition of a removal of a gas-air mixture without breaching into the room.

Keywords: exhaust ventilation, ventilation hood, simulation, heat-treatment chamber, numerical experiment